Ich habe eine Back-UPS CS 500 an einen Linux-PC (openSUSE 13.1 x86_64) angeschlossen, der seit heute Morgen meldet
BCHARGE : 000.0 Percent
TIMELEFT : 0.0 Minutes
Die anderen Werte erscheinen mir normal:
$ apcaccess
APC : 001,045,1097
DATE : 2016-06-15 13:04:52 +0000
HOSTNAME : myhost
VERSION : 3.14.10 (13 September 2011) suse
UPSNAME : myups
CABLE : USB Cable
DRIVER : USB UPS Driver
UPSMODE : Stand Alone
STARTTIME: 2016-06-15 12:05:21 +0000
MODEL : Back-UPS CS 500
STATUS : ONLINE LOWBATT
LINEV : 226.0 Volts
LOADPCT : 16.0 Percent Load Capacity
BCHARGE : 000.0 Percent
TIMELEFT : 0.0 Minutes
MBATTCHG : 5 Percent
MINTIMEL : 3 Minutes
MAXTIME : 0 Seconds
OUTPUTV : 230.0 Volts
SENSE : Medium
DWAKE : 000 Seconds
DSHUTD : 000 Seconds
LOTRANS : 180.0 Volts
HITRANS : 266.0 Volts
RETPCT : 000.0 Percent
ITEMP : 29.2 C Internal
ALARMDEL : 30 seconds
BATTV : 12.0 Volts
LINEFREQ : 50.0 Hz
LASTXFER : Low line voltage
NUMXFERS : 0
TONBATT : 0 seconds
CUMONBATT: 0 seconds
XOFFBATT : N/A
SELFTEST : NO
STESTI : None
STATFLAG : 0x07000048 Status Flag
MANDATE : 2010-08-17
SERIALNO : 4B1034P03420
BATTDATE : 2010-08-17
NOMOUTV : 230 Volts
NOMINV : 230 Volts
NOMBATTV : 12.0 Volts
NOMPOWER : 300 Watts
FIRMWARE : 808.q8.I USB FW:q8
END APC : 2016-06-15 13:05:08 +0000
Handelt es sich hier vielleicht um einen Firmware-Fehler? Der Wert "000.0" kommt mir wirklich merkwürdig vor...
Aktualisieren
Nun scheint sich die Batterie wieder etwas aufgeladen zu haben, aber sie scheint bei 14 % hängengeblieben zu sein:
$ apcaccess
APC : 001,045,1089
DATE : 2016-06-16 19:19:03 +0000
HOSTNAME : myhost
VERSION : 3.14.10 (13 September 2011) suse
UPSNAME : myups
CABLE : USB Cable
DRIVER : USB UPS Driver
UPSMODE : Stand Alone
STARTTIME: 2016-06-15 14:08:31 +0000
MODEL : Back-UPS CS 500
STATUS : ONLINE
LINEV : 226.0 Volts
LOADPCT : 17.0 Percent Load Capacity
BCHARGE : 014.0 Percent
TIMELEFT : 5.5 Minutes
MBATTCHG : 5 Percent
MINTIMEL : 3 Minutes
MAXTIME : 0 Seconds
OUTPUTV : 230.0 Volts
SENSE : Medium
DWAKE : 000 Seconds
DSHUTD : 000 Seconds
LOTRANS : 180.0 Volts
HITRANS : 266.0 Volts
RETPCT : 000.0 Percent
ITEMP : 29.2 C Internal
ALARMDEL : 30 seconds
BATTV : 12.2 Volts
LINEFREQ : 50.0 Hz
LASTXFER : Low line voltage
NUMXFERS : 0
TONBATT : 0 seconds
CUMONBATT: 0 seconds
XOFFBATT : N/A
SELFTEST : NO
STESTI : None
STATFLAG : 0x07000008 Status Flag
MANDATE : 2010-08-17
SERIALNO : 4B1034P03420
BATTDATE : 2010-08-17
NOMOUTV : 230 Volts
NOMINV : 230 Volts
NOMBATTV : 12.0 Volts
NOMPOWER : 300 Watts
FIRMWARE : 808.q8.I USB FW:q8
END APC : 2016-06-16 19:19:03 +0000
Antwort1
Nein, das ist normales Verhalten.
Ihre Batterie stammt aus dem Jahr 2010 und ist einfach kaputt gegangen. Die Lebensdauer einer USV-Batterie beträgt normalerweise etwa 5 bis 6 Jahre.
Ihre Batterie muss ausgetauscht werden. Ich kenne mich mit dieser Art von USV nicht aus und weiß daher nicht, ob Ersatzbatterien verkauft werden oder ob Sie die gesamte Einheit austauschen müssen. Wenn ein Austausch der Batterie möglich ist, ist es günstiger.