오늘 아침부터 Linux PC(openSUSE 13.1 x86_64)에 Back-UPS CS 500이 연결되어 있다고 보고했습니다.
BCHARGE : 000.0 Percent
TIMELEFT : 0.0 Minutes
다른 값은 나에게 정상적인 것 같습니다.
$ apcaccess
APC : 001,045,1097
DATE : 2016-06-15 13:04:52 +0000
HOSTNAME : myhost
VERSION : 3.14.10 (13 September 2011) suse
UPSNAME : myups
CABLE : USB Cable
DRIVER : USB UPS Driver
UPSMODE : Stand Alone
STARTTIME: 2016-06-15 12:05:21 +0000
MODEL : Back-UPS CS 500
STATUS : ONLINE LOWBATT
LINEV : 226.0 Volts
LOADPCT : 16.0 Percent Load Capacity
BCHARGE : 000.0 Percent
TIMELEFT : 0.0 Minutes
MBATTCHG : 5 Percent
MINTIMEL : 3 Minutes
MAXTIME : 0 Seconds
OUTPUTV : 230.0 Volts
SENSE : Medium
DWAKE : 000 Seconds
DSHUTD : 000 Seconds
LOTRANS : 180.0 Volts
HITRANS : 266.0 Volts
RETPCT : 000.0 Percent
ITEMP : 29.2 C Internal
ALARMDEL : 30 seconds
BATTV : 12.0 Volts
LINEFREQ : 50.0 Hz
LASTXFER : Low line voltage
NUMXFERS : 0
TONBATT : 0 seconds
CUMONBATT: 0 seconds
XOFFBATT : N/A
SELFTEST : NO
STESTI : None
STATFLAG : 0x07000048 Status Flag
MANDATE : 2010-08-17
SERIALNO : 4B1034P03420
BATTDATE : 2010-08-17
NOMOUTV : 230 Volts
NOMINV : 230 Volts
NOMBATTV : 12.0 Volts
NOMPOWER : 300 Watts
FIRMWARE : 808.q8.I USB FW:q8
END APC : 2016-06-15 13:05:08 +0000
혹시 펌웨어 버그일까요? "000.0" 값이 정말 이상한 것 같아요...
업데이트
이제 배터리가 약간 충전된 것 같지만 14%에서 멈춰 있는 것 같습니다.
$ apcaccess
APC : 001,045,1089
DATE : 2016-06-16 19:19:03 +0000
HOSTNAME : myhost
VERSION : 3.14.10 (13 September 2011) suse
UPSNAME : myups
CABLE : USB Cable
DRIVER : USB UPS Driver
UPSMODE : Stand Alone
STARTTIME: 2016-06-15 14:08:31 +0000
MODEL : Back-UPS CS 500
STATUS : ONLINE
LINEV : 226.0 Volts
LOADPCT : 17.0 Percent Load Capacity
BCHARGE : 014.0 Percent
TIMELEFT : 5.5 Minutes
MBATTCHG : 5 Percent
MINTIMEL : 3 Minutes
MAXTIME : 0 Seconds
OUTPUTV : 230.0 Volts
SENSE : Medium
DWAKE : 000 Seconds
DSHUTD : 000 Seconds
LOTRANS : 180.0 Volts
HITRANS : 266.0 Volts
RETPCT : 000.0 Percent
ITEMP : 29.2 C Internal
ALARMDEL : 30 seconds
BATTV : 12.2 Volts
LINEFREQ : 50.0 Hz
LASTXFER : Low line voltage
NUMXFERS : 0
TONBATT : 0 seconds
CUMONBATT: 0 seconds
XOFFBATT : N/A
SELFTEST : NO
STESTI : None
STATFLAG : 0x07000008 Status Flag
MANDATE : 2010-08-17
SERIALNO : 4B1034P03420
BATTDATE : 2010-08-17
NOMOUTV : 230 Volts
NOMINV : 230 Volts
NOMBATTV : 12.0 Volts
NOMPOWER : 300 Watts
FIRMWARE : 808.q8.I USB FW:q8
END APC : 2016-06-16 19:19:03 +0000
답변1
아니요, 이는 정상적인 동작입니다.
귀하의 배터리는 2010년에 출시되었으며 수명이 다했습니다. UPS의 배터리 예상 날짜는 일반적으로 약 5~6년입니다.
배터리를 교체해야 합니다. 저는 이러한 유형의 UPS에 익숙하지 않기 때문에 교체용 배터리를 판매하는지 아니면 장치 전체를 교체해야 하는지 잘 모르겠습니다. 배터리 교체가 가능하다면 가격은 더 저렴해집니다.